r***x 发帖数: 108 | 1 房子inspection 的时候,inspector 说 GAS Line 没grounding, a violation of the
CSST code.
Inspector 原话是: "CSST" used for Gas Lines, Gas Line System is not bonded
to electical ground system, recommend bonding for safety to prevent fire.
自己search了一下,
7.13.2 CSST. CSST gas piping systems shall be bonded to the electrical
service grounding electrode system at the point where the gas service enters
the building.The bonding jumper shall not be smaller than 6 AWG copper wire
or
equivalent.
想自己DIY, 请问是不是买一个ground clamp 夹在gas line上, 然后clamp 连接一根6
awg 铜线,铜线的另一头连接breaker box (electical panel) 的grounding bar.
多谢指点。 |
f****i 发帖数: 20252 | 2 在炉子那里接到冷水管就行
the
equivalent.
【在 r***x 的大作中提到】 : 房子inspection 的时候,inspector 说 GAS Line 没grounding, a violation of the : CSST code. : Inspector 原话是: "CSST" used for Gas Lines, Gas Line System is not bonded : to electical ground system, recommend bonding for safety to prevent fire. : 自己search了一下, : 7.13.2 CSST. CSST gas piping systems shall be bonded to the electrical : service grounding electrode system at the point where the gas service enters : the building.The bonding jumper shall not be smaller than 6 AWG copper wire : or : equivalent.
|
s**********d 发帖数: 36899 | |
r***x 发帖数: 108 | 4 接到冷水管的方法,网上有人说不太好,如果水管因为维修断开了,就可能不是连接地
线了。
【在 f****i 的大作中提到】 : 在炉子那里接到冷水管就行 : : the : equivalent.
|
f****i 发帖数: 20252 | 5 符合code就行
水管又不是天天维修
【在 r***x 的大作中提到】 : 接到冷水管的方法,网上有人说不太好,如果水管因为维修断开了,就可能不是连接地 : 线了。
|
r***x 发帖数: 108 | 6 gas line 的地线是为了防止闪电,接breker box的壳,只能防静电吧。俺真的不懂。
【在 s**********d 的大作中提到】 : 接到breaker box的壳上就行。
|