由买买提看人间百态

topics

全部话题 - 话题: 24v
首页 上页 1 2 3 4 5 6 7 8 9 10 (共10页)
a*********s
发帖数: 26
1
昨天暖气不工作了。我的暖气炉型号是 NTG9125FKA1.点火方式是用hot surface
ignitor(HSI).用万用表测了电阻式5.5欧。控制器是smart valve(SV9500M2674).
测了一下到HSI的电压是24V。无论是输出电压还是HSI的电阻都正常,但是HSI就是不红
。所以燃气就点不着。imore和各位大侠知道哪里出问题了吗?多谢!
i***e
发帖数: 9429
2
spare的线用做“C”线没问题, 接到易哭鼻上的“C”端后, 同样要打开furnace, 确
认这根spare线是否接在Carrier furnace 电路板上的“24V COM” 端/“C”端。
i***e
发帖数: 9429
3
接线没错/
你去量furnace电路板上的接线: “C”和“R”之间是否有24V?按下弹簧开关量或暂
时用黑胶布贴紧。
w*******b
发帖数: 21
4
谢谢你的信息。
c线肯定没有接到其它地方,但是通电后furnace像打鼓似的响声。将furnace的c线接上
后,blower开始运行,但是不点火,所以只有冷风出来。
换上旧的温控器后也是这样:blower运行,但是不出热风。
我觉得可能是变压器坏了。因为用万用表测primary端是110v,但是sec端是0.所以相当
于控制板就没有24v的电。然后blower的运行不需要控制板上的电压。不知道我的推测
对不对?已经定了一个变压器,晚上试试看。
另外我在网上查了一下,我这个furnace是上个世纪80年代的,控制板很老,不是集成
电路的,也没有那个led指示灯。不知道怎么排查故障。可能需要换个先进点的控制板。
c****e
发帖数: 749
5
听上去像是24v power supply坏了。如果没记错的话,应该在indoor unit 里有个120
转24的变压器来提供低压。可能是那个烧了。就二三十刀的东西。不过我瞎猜的啊。

呢?
unit
c****e
发帖数: 749
6
来自主题: Living版 - 空调求救
我猜很有可能是contactor的线圈或24v变压器坏了。
s****2
发帖数: 921
7
来自主题: Living版 - 空调求救
24v变压器坏了, thermostat还能工作吗?
s****2
发帖数: 921
8
来自主题: Living版 - 空调求救
帽子打开没有24v
s******4
发帖数: 1221
9
来自主题: Living版 - 求助 空调室外机风扇不转了
update : 刚才把电容装回去,量了电压实正常的,246, 246, 24v, 拨动了一下风
扇转起来了。 但是没有冷风,摸了下压缩机比较烫, 粗的铜管和细的铜管都是常温
。 请问大神门,这是压缩机坏了么?还可以自己尝试解决么?
i***e
发帖数: 9429
10
来自主题: Living版 - 空调不工作了。请教。
初步猜测可能是电池腐蚀引起的24V温控器短路。
i***e
发帖数: 9429
11
一般还有两种可能也很常见,也经常提到的。
外机 里的contactor
制冷剂漏了, 压力不足,低压保护装置"OPEN".
首先你要确认有24V到外机。
w****g
发帖数: 1143
12
啊,研究了一下,搞清楚一些东西。问题是怎么确认24V到contactor啊?
i***e
发帖数: 9429
13
打开外机面板, 一般是从墙里出来沿着管道有一根细线,有两个小wirenuts 和外机上
的24V控制线对接。 拧开来 测那两根线之间(空调要开着测)。
w****g
发帖数: 1143
14
这个24V居然是AC,是有的。contactor也工作,通电了,那两块铜片就合上了。
那接着就是要测氟利昂的压力了?哪里有卖测压力的表啊?值得买一个还是找人来修算
了?自己也没法灌氟利昂啊。
m****a
发帖数: 274
15
来自主题: Living版 - carrier AC kept blowing 3A fuse
下午回家发现楼上的T stat彻底黑掉了,拆了T stat面板,发现R 和 C 之间只有11 V
,而不是24V,上阁楼一看carrier空调里3A保险丝烧了,找了youtube,看着换个保险
丝也不难,想着晚上要休息,就把楼下zone的好的保险丝换上来,插上T stat面板发现
还是无法启动,发现新换的保险丝也断了,试问imore 版主和各位行家,这个怎么破?
i***e
发帖数: 9429
16
来自主题: Living版 - 请教:空调烧保险丝
明显接得不对。contactor 上的24V 负线不应该接在壳子的地线上。
这也算是蛮好的机子, 不应该是TRANE dealer 装出来的。或者另有隐情?
F***Q
发帖数: 6599
17
来自主题: Living版 - Cordless Mower好用吗?

I have an older model, 24V. used for 4 years, problem free.
z*****n
发帖数: 413
18
来自主题: Living版 - 也问空调的问题
多谢楼上两位,今天爬楼换了保险丝,还是没有用。然后想有没有可能是变压器坏了?
根据这个文件里的fig16,(http://dms.hvacpartners.com/docs/1010/public/09/wd-fancoil-04.pdf)用简易电笔测了一下,连变压器的230一面都有电,24v那边red有电,brn没有电。这个正常吗?不过看变压器表面好像没有异样。
不过speed tap connections的blue和wht都没有电。可能是别的什么问题吗?
再谢!
n***s
发帖数: 10056
19
来自主题: Living版 - 也问空调的问题
从fig16看, 在transformer处RED和BRN之间应有24v. 你的应该没有。从这里推测--
transformer坏了。
n***s
发帖数: 10056
20
来自主题: Living版 - 也问空调的问题
Check manual for correct fuse amperage. Mine is 3A.
When you measured voltage between RED and BRN, did you see 0 or 24v?
f****h
发帖数: 443
21
来自主题: Living版 - Greenworks 24v cordless trimmer deal
来晚了,gone
t****t
发帖数: 610
22
We had this discussion before. I just got an idea:
Install the motorized damper only. Connect it to a 24v transformer. The
transformer is plugged into a remote control receptacle
https://www.amazon.com/Etekcity-Wireless-Electrical-Household-Appliances/dp/
B0087EIDRS.
Then the damper can be controlled remotely, although not automatic. How does
this sound?
i***e
发帖数: 9429
23
你的温控器上如果只接上“R”,“W”,“G”和“Y”,你是测不到24V的。
没有测电压的必要。
z*****n
发帖数: 447
24
https://www.worx.com/24v-cordless-lawn-mower-wg775.html
南加州小院子,前后大概3000sqf, 估计2周割一次,找来找去,发现这款似乎性价比最
高,就是不知电池经用么,希望可用个3年,不知有何建议,谢谢!
F***Q
发帖数: 6599
25

150
个)
I have two craftman impact drivers (one for work, one for home), both of
them work well. I especially love the right-angle one, unfortunately it was
disconnected.
http://www.craftsman.com/products/craftsman-17428-nextec-12-volt-cordless-compact-1-4-impact-driver
http://www.searsoutlet.com/Nextec-12-0-Volt-Right-Angle-Impact-Driver/d/product_details.jsp?pid=64513&mode=seeAll
I have a cordless 24V black&decker, used for 5 years, zero problem, zero
maintenance.

发帖数: 1
26

汇报:
升高温控器温度,INDUCED DRAFT MOTOR 不能启动,此时control board 没有error
code, 见图。control board的mircroprocessor led是on,电表测量control board w
to c 是24v,说明control board没有坏。转到下一个部件 - limit switch, 拆下,测
量是0, 说明是闭合状态,没有问题,但是已经生锈,需要更换新件。再转到
pressure switch, 再次开启furnace一分钟,switch wire接口测量依据是0,说明
pressure switch是open状态,问题找到了。到century a/c买件,被拒,没有license,
最后找熟人借license,才买到,型号不同,但是装后效果还可以。
z*****8
发帖数: 2546
27
来自主题: Living版 - help! Gas furnace has flame but no heat
多谢回答。没搞过HVAC,还请多帮忙。 不知电工接的thermostat 对不对,this unit
has 4 terminal for wire, but he uses 4 wires to connect the 24v thermostat
C=not connected
G=connects to green
Y=connects to black (this could be the furnace)
W=white
R=red
I did more experiments:
1. turn thermostat from off to heat: blower start immediately, but no heat
2. turn thermostat from heat to off: blower stops after a few seconds delay,
but during the few seconds, I swear it is warm air.
attached are some images, I label them A,B,C,D,.... 阅读全帖
z*****8
发帖数: 2546
28
来自主题: Living版 - help! Gas furnace has flame but no heat
OK, I will check the contactor tomorrow if it does not rain too hard.
I expect there is no 24V low volt power to the coil, but the contactor
somehow has shorted the contacts (closed the switch) providing power to the
AC. Is this your diagnosis strategy? This would be a good thing to check,
thank you very much.
z*****8
发帖数: 2546
29
来自主题: Living版 - help! Gas furnace has flame but no heat
tested the power contactor today. There was 24V on the contactor. Since now
I have
the circuit diagram, I spent some time tracing the circuit, I found the
electrician made two mistakes connecting the thermostats. The first mistake
was the Y and W wires at the thermostats were shorted (the control wires are
stranded type, he did not do a clean job), the second mistake was he
swapped Y and W. This would explain why I can see flame and the contactor is
turned on.
Now the heat is working!!!
Thanks i... 阅读全帖
y*j
发帖数: 3139
30
来自主题: Living版 - help! Gas furnace has flame but no heat
这位电工是色盲吗?

:tested the power contactor today. There was 24V on the contactor. Since
now I have
:the circuit diagram, I spent some time tracing the circuit, I found the
:electrician made two mistakes connecting the thermostats. The first
mistake was the Y and W wires at the thermostats were shorted (the control
wires are stranded type, he did not do a clean job), the second mistake was
he
:swapped Y and W. This would explain why I can see flame and the contactor
is turned on.
:Now the heat is wor... 阅读全帖
i***e
发帖数: 9429
31
来自主题: Living版 - FURNACE NO GAS FLOW IN
如果点火器有发亮(完全发亮),说明点火器没问题。
4个最有可能的情况
Burner 上积灰尘, 没点着。你会听到有气出来的声音。
没有24V 电到gas valve. 需测量确认。
gas valve 坏了。
天然气管道里没有气或gas 压力不足。
当然不排除还有其它情况,只是我还没想到。
i***e
发帖数: 9429
32
来自主题: Living版 - FURNACE NO GAS FLOW IN
如果点火器有发亮(完全发亮),说明点火器没问题。
4个最有可能的情况
Burner 上积灰尘, 没点着。你会听到有气出来的声音。
没有24V 电到gas valve. 需测量确认。
gas valve 坏了。
天然气管道里没有气或gas 压力不足。
当然不排除还有其它情况,只是我还没想到。
d*******1
发帖数: 2253
33
来自主题: Living版 - FURNACE NO GAS FLOW IN
老问题又出现了,入冬以来一直工作正常,今天早上突然就又点不着火了,有几次火先
点着了,过了几秒钟就灭了。我就把unit 断电了几个小时,现在第三次点火就又点着
了。很是头疼!怎么回事呢?
[在 imore (imore) 的大作中提到:]
:如果点火器有发亮(完全发亮),说明点火器没问题。
:Burner 上积灰尘, 没点着。你会听到有气出来的声音。
:没有24V 电到gas valve. 需测量确认。
:gas valve 坏了。
:天然气管道里没有气或gas 压力不足。
:当然不排除还有其它情况,只是我还没想到。

发帖数: 1
34
来自主题: Living版 - 请推荐一下电钻
https://m.costco.com/Greenworks-24V-Drill-Driver-and-Impact-Driver-Combo.
product.100301083.html
穷人买了这个
不是真无级变速,不过扭力蛮大的
k***5
发帖数: 393
35
测了一下capacitor, 是好的。45 uF 和5 uF。
进入control box的线是有240左右,不过outside unit(condenser和fan)一点反应一
点声音都没有。
control box里面很简单,只有capacitor和contact,没看到control board。
测了一下24V,(是测contact的两边吗?)没测到,不知道是不是测错了?
k***5
发帖数: 393
36
还没有研究过thermostat,不过用heat和只用Fan都没问题。所以我假定它的没问题的。
另外有power进入contactor,只是没有power出来。是不是就是contactor的问题,还是
有可能thermostat没法给出24V?这样区分是contactor的问题还是thermostat的问题?
k***5
发帖数: 393
37
多谢各位支招!
step1 没测,不过fan是work的,所以应该没问题。
step2 测了。没测到24V, 不过没注意click声,就注意了室内风扇想了。测的方法就是
测contactor两边。今天回家重测一下。另外我单独观察thermostat时听到了click声。
就是没在那时去测电压。
step4 测了。capacitor没问题。45 uf和 5 uf都是对的。
k***5
发帖数: 393
38
啊?晕了。我一直以为是测contactor两边。
内机出来的24V到哪儿去找?就在外面的control box里还是要上阁楼去找?
k***5
发帖数: 393
39
进入外机的24V线找到了。当thermostat工作时,这两线的电压是27V,不工作时是0V。
所以内机应该是没有问题的。
contactor两侧总是0V。
p*******g
发帖数: 92
40
来自主题: Living版 - 请大家帮忙看看HVAC报价
坐标北加州,SFH,furnace很新,不用换,房子面积1200 sqft。问了好几个local的
HVAC小公司,基本给报价的都是两款机器3TON 14SEER的carrier或者2.5TON 14SEER的
Bryant, model # 105ANA 两个都要4800左右,贵的报价都5500了,想问问大家这个价
钱合理不,有个yelp review 170的说carrier要是愿意付cash,可以再便宜100。这个
价钱靠谱么,谢谢大家,也欢迎imore等大牛给点建议。
CARRIER AIR CONDITIONING INSTALLATION 4,800.00
1-24AAA536 3TON 14SEER COMFORT SERIES AIR CONDITIONER
1-A.D.P. C36175 DOWNFLOW COIL
1- 50 X 3/4 A/C LINE SET
1-30 AMP x 230 VOLT ELECTRICAL CIRCUIT
1-3/4" PVC DRAIN
1-BUILD SHEETMETAL BASE TO ELEVATE COIL
1-ALL N... 阅读全帖
z******e
发帖数: 676
41
来自主题: Living版 - 空调问题, 求指教
感谢imore大神. 24V没有是R线没有, 温控器完全是好的.
s******2
发帖数: 852
42
blower 不动了不代表是blower坏了
先说说你都查了些啥,air handler的24v,240v都查了吗
i***e
发帖数: 9429
43
来自主题: Living版 - 请教一个hvac的问题
所谓的內机能听见unit运行的声音,也就是FAN的声音。
如果很确定fan也停止了工作,如果从內机里发出声音,也就意味着某个零件开始出问
题,最长发生的是24V变压器发出的声音。
当然在没有了解真实状况前,我也是根据你的描述猜测的。

发帖数: 1
44
电表先量一下switch,有些switch会烧掉,换一个就好了,若switch有电,测
transformer是否有24v出来给control board。
d*******l
发帖数: 575
45
来自主题: Living版 - 空调不制热了是怎么回事?
thermostat click仅表示close了, 你还是要用电表去阁楼上按operation sequence逐
一测量,比如说第一步控制面板上W terminal是不是有24v电压。。。。
B********n
发帖数: 12753
46
来自主题: Living版 - 一个关于ecobee或nest的问题
打算把老式的thermometer换成nest或是ecobee
家里的系统是heat boilers通过relay连接成了2个zone
relay里接着2根线,分别是接在控制器上的W和R
老式的控制器有G W Y R RC接着的,C wire留空
但是在relay里有一根枚红色的预留线,可以直接接relay的C
nest和ecobee都没有R这个接口,只有RH和RC
问他们两家的客服,都回答我说的是R和Rc之间是jumper,我说没有jumper,R来自heat
,Rc来自AC cooling部分,于是他们就搞不懂了
ecobee的客服更搞笑,非要和我你的C不可以用heat里来的C,一定要用AC里来的C,我
说C只是提供电源,有区别么?然后他非要说 The thermostat is designed that way
I'm afraid. C is a route back to the negative of the transformer the
thermostat is receiving 24V from, when we have two power sources e... 阅读全帖
m*******p
发帖数: 1978
47
Needs a new doorbell transformer, at least 16v, up to 24v.
p*******m
发帖数: 20761
48
我的门铃是NuTone CD131SWH
16v 可以用吗


: Needs a new doorbell transformer, at least 16v, up to 24v.

i***e
发帖数: 9429
49
不断电绝对死不了人。
最坏可能 --- 轻重如下:
换电路板上的保险丝
换24V变压器
换电路板

发帖数: 1
50
这个是24v低压,电不死人。
我换的时候从来没断过电(换过好多次)。但换的时候如果不断电千万小心别让这些线
相互碰到。有一次大意把两条线短路,结果烧掉了保险丝。当时不懂,看空调不工作了
就找人来修,花了50块labor,就是换了个保险丝
首页 上页 1 2 3 4 5 6 7 8 9 10 (共10页)