d****9 发帖数: 58 | 1 屋内temperature differential (between 进风口与出风口?)只有11F, inspector说
至少要高于14F才满足要求。
请问什么原因会造成这个问题?
多谢指教!! | g*****9 发帖数: 4125 | 2 You maybe ok.
If you are in northern part (very short cooling season and does not get very
hot outside) more than 10F temperature differential is good enough.
You need to measure the temperature differential after the system has been
running for a while (not you just turn on), uninsulated duct could take more
than 30min for the system to stablize. Also did you measure in the room
closest to the AC for furtherest away from the AC.
Also it is harder for AC to main the temperature differential if y
【在 d****9 的大作中提到】 : 屋内temperature differential (between 进风口与出风口?)只有11F, inspector说 : 至少要高于14F才满足要求。 : 请问什么原因会造成这个问题? : 多谢指教!!
| d****9 发帖数: 58 | 3 Hi gezhi89, thank you so much for your reply!! I have enjoyed reading many
of your 贴子。 也很欣赏你热心帮助家居生活新手!
Below is the words that I copied from the inspection report. The temperature
differential is between the intake and the output. The AC is brandnew and
had been running for a few days before the measurement was taken.
I am going to meet with the HVAC contractor tomorrow. Any suggestions about
what I should ask him? |
|